CVE-2025-30002 is a high-severity SQL injection vulnerability affecting all versions of Siemens TeleControl Server Basic prior to V3.1.2.2. An authenticated remote attacker can exploit this flaw via the 'UpdateConnectionVariables' method to bypass authorization, manipulate the database, and execute code with "NT AUTHORITY\NetworkService" privileges by accessing port 8000. The vulnerability has a CVSS score of 8.8 (High) due to its network attack vector, low complexity, and high impact on confidentiality, integrity, and availability. Currently, there is no evidence of active exploitation, public exploit code, or significant community discussion surrounding this CVE.
| Vendor | Product | Version(s) | CPE |
|---|---|---|---|
< 3.1.2.2CPE matchmatch criteria | cpe:2.3:a:siemens:telecontrol_server_basic:*:*:*:*:*:*:*:* | ||
>= 0, < V3.1.2.2CPE match | cpe:2.3:a:siemens:telecontrol_server_basic:*:*:*:*:*:*:*:* |
CVSS version used by this source: 4.0
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
The average CVE in this peer group has 0.0 Twitter, 0.0 Reddit, 0.3 Bluesky, 0.1 Mastodon, and 0.2 GitHub mentions.
No media coverage found for this CVE.
The average CVE in this peer group has 0.1 InfoSec Media, 0.0 Vendor Blog, and 0.0 Security Researcher mentions.
Remediation records are not available for this CVE.